Home » Products » UPS (Uninterruptible Power Supply) » G-GM Series 1-3kVA UPS

1-3kVA UPS

1-3kVA UPS

Application of G-GM Series 1-3kVA UPS
G-GM series 1-3kVA can be applicable to servers, data centers, critical network devices, sensitive electronic equipment, telecommunications, etc.

Features of G-GM Series 1-3kVA UPS
1. Designed with online double conversion technology, and employs advanced microprocessor control.
2. Wide input voltage range.
3. Zero transfer time.
4. Protection against all types of power problems.
5. Self test while starting the UPS.
6. Site wiring fault warning.
7. On-battery power-on function.
8. Smart RS232 communication interface.
9. Intelligent slot is available.
10. Sealed, lead-acid, and maintenance free battery.

Technical Specifications

Model G1K G2K G3K G1KS G2KS G3KS
GM1K GM2K GM3K GM1KS GM2KS GM3KS
Capacity VA/W 1kVA/
0.7KW
2kVA/
1.4KW
3kVA/
2.1KW
1kVA/
0.7KW
2kVA/
1.4KW
3kVA/
2.1KW
Input Nominal voltage 110/115/120 VAC or 220/230/240 VAC
Voltage range 180-300VAC
Frequency range 50Hz, 46-54Hz, 60Hz, 56-64Hz.
Phase Single phase
Power factor >0.97
Connection IEC320
-10A inlet
IEC320
-10A inlet
IEC320
-16A inlet
IEC320
-10A inlet
IEC320
-10A inlet
IEC320
-16A inlet
Output Voltage 110/115/120× (1±2%) VAC, 220/230/240×(1±2%)VAC
Frequency Synchronization range (line mode), 50 or 60Hz×(1±0.2%) (Battery mode)
Phase Single phase
Wave form Sine wave
Power factor 0.7 or 0.8 optional
Voltage distortion 3% 4% 4% 3% 4% 4%
Overload capability 110%-150% for 30 sec., ≥150% for 200 ms
Current crest radio 3: 1
Connections IEC320*4 IEC320*6 IEC320*3 terminal block IEC320*4 IEC320*6 IEC320*3
terminal block
Battery and charge Type Sealed, maintenance free, and lead-acid
Nominal DC to voltage 36VDC 96VDC 96VDC
Quantity 3 pieces 8 pieces 8 pieces Depends on the requested back-up time
Back-up time(full load) 5 min 9 min 5min Depends on the capacity of the external battery bank
Recharge time 5 hrs to 90% of capacity Depends on the capacity of the external battery bank
Automatic transfer On overload and UPS failure
Before UPS power-on Default 'ON' user adjustable to 'YES'
Voltage range 40-132VAC (default), user can adjust the voltage within 40-143VAC; 80-264VAC (default), user can adjust the voltage within 80-286VAC.
Transfer time AC to DC zero Inverter to bypass 4 ms (typical)
Indicators UG/LED display Load level / battery / lever, battery, utility power, inverter, bypass, overload, fault
UX/LCD display UPS status, I/P and O/P voltage and frequency, battery voltage, battery capacity, loading, temperature, history record
Audible alarm Bypass, on battery mode, battery low, overload, fault
Acoustic noise At 1 meter distance <45 dB <50 dB <50 dB <45 dB <50 dB <50 dB
Communications DB-9 port PS-232 serial interface
Intelligent slot Options: SNMP card, AS400 card or Win power CMC / (USB port)
Environment Operating temperature 0-40℃
Operating humidity 20-90% non-condensing
Weight Net(Kg) 13 31.5 32 7 13.5 14
Dimensions (package) W ×D ×H (mm) 240×495
×335
335×590
×480
355×590
×480
240×495
×335
335×590
×480
335×590
×480

As a primary UPS product manufacturer in China, Higred Power (Wuhan) Co., Ltd. is dedicated to produce high quality off line UPS, high frequency online UPS, low frequency online UPS, and more. Those products employ advanced digital control technology, and have strong extended function. Currently, our products are CE certified and exported to the United States, Russia, Austria, Brazil, and other countries as a result of high quality and economical prices.

Please do contact Higred Power (Wuhan) Co., Ltd., should you require further information on our products or for orders via email or phone.

Related Products
  • G / GM Series 6 - 20kVA G - GM series 6-20kVA is widely applied to servers, data centers, critical network devices, sensitive electronic equipment, telecommunications, etc...