Application of HP9330C series 20-80kVA UPS
HP9330C series 20-80kVA UPS is particularly applicable to severs, data centers, critical network devices, sensitive electronic equipment, telecommunications, etc.

Features

1. N+X parallel redundancy
The maximum of the inbuilt parallel mode is 8 pieces of UPS. In addition, battery is compatible in the parallel mode.

2. High-efficient DSP chip
Installed with digital DSP controlling chip, HP9330C series UPS products have precise data processing capacity. Furthermore, it is stable in output, and reliable in performance.

3. Outstanding electric property
The efficiency of the machine is 93%, and even reaches over 98% in the EC mode. The input power factor is as high as 0.99.

4. Twin-channel line input
HP9330C series UPS products can offer you safe power supply. You can choose either two-line input or one-line input according to the actual condition. Besides, smart battery is available.

Technical Parameters of HP9330C series 20-80kVA UPS

Product series High Frequency Online UPS 20-80kVA (3PH/3PH)
Model 20K 20K-
XL
30K 30K-
XL
40K 40K-
XL
60K-
XL
ISO
80K-
XL
ISO
Capacity VA/W 20KVA
/16KW
20KVA
/16KW
30KVA
/24KW
30KVA
/24KW
40KVA
/32KW
40KVA
/32KW
60KVA
/48KW
80KVA
/64KW
Rectifier input Rectifier type IGBT-based vector controlled PFC (PF corrected)
Input voltage 380/400/415VAC(Accepted from 305 to 477 with ptebatt.use)
Input frequency 50 or 60 Hz (accepted from 40 to 70)
Input current THD 3% (without any filter)
Input power factor ≥0.99 (with any filter)
Power walk-in 5 to 30s (selectable)
Bypass input Input voltage 380/400/415VAC
Battery Battery type VRLA (valve regulated lead acid) or wet / flooded or NiCd
End-cell voltage Selectable from 1.60 to 1.90Vdc / Cell (for VRLA)
DC ripple current(float) <5% (of C 10 AH capacity) RMS value
DC ripple voltage
(float and const V Ch)
<1% (RMS value)
Temp.conp. Charge Standard (where internal batteries is 10,15,20,30,40 kVA) and
optional (for all other battery configurations)
Output Inverter type IGBT-based vector, repetitive and PI controlled
Output voltage 380/400/415VAC ± 0.5 regulation (3-phase RMS average)
Output frequency 50 or 60Hz with ± 0.05 regulation
Output voltage THD 1% (max)
Max. load crest factor 3:1 (compliant with IEC 62040-3)
Transient Volt. Resp 10ms to recover ± 5% of nominal voltage for 0% to 100%
or 100% to 0% step load
Max. leading PF load Up to 0.9
Voltage displacement 120° ± 10° (with100% unbalanced load)
Overload 110% for 60 minutes,125% for 10 minutes,150% for 1 minute
Efficiency AC-AC Up to 0.9
EMC-class Class - A (applicable for both radiated and conducted)
Environmental Storage temperature -20 to 70℃ (UPS) and 25 ± 5 (battery)
Operating temperature 0 to 40℃ (UPS)and 25 ± 5 (battery)
Relative humidity 0 to 95% (non-condensing)
Maximum altitude above
mean sea level
1000m (as per IEC 62040/3)
Main unit Dimension (W×D×H) mm 420
X600
X1250
420
X600
X950
470
X700
X1750
470
X700
X1150
470
X700
X1750
470
X700
X1150
3600
X800
X1850
3600
X800
X1850
Weight(kg) 158 82 220 110 224 114 282 306
UPS enclosure IP IP 20 (even with open front door)

Standard
IEC 62040-3             EN 50091-1-1       ANSI C62.41 (IEEE 587)
IEC 62040-2             EN 50091-2
IEC 62040-1-1         EN 50091-3
IEC 60146-1-1         EN 60950
IEC 61000-4-2, 4, 5,6, 8,11                   EN 60529